Short Description:
Features 1.Any position mounting 2.Interchangeable mounting plate 3.Low wattage coil 4. Double break contacts ensure positive make and break. Specifications Contact block and carrier are high quality electrical-grade thermosetting resin
Designed for central air conditioning and heating equipment
Features
1.Any position mounting
2.Interchangeable mounting plate
3.Low wattage coil
4. Double break contacts ensure positive make and break.
Specifications
Insulating material | Contact block and carrier are high quality electrical-grade thermosetting resin |
Temperature range | -40℃ to 150℃ |
Mechanical life (no load) | Conforms to UL and ARI specifications |
Electricl life | Conforms to UL and ARI specifications |
Weight (approximate) | 16 oz |
Coils Frequency | 50/60Hz |
Coil insulation | Class B(130oC ) 24 through 208/240 Volts AC |
Termination | Pressure connector and double 1/4 Q.C |
Operate | 85% of nominal coil voltage; 110% maximum safe operate |
Duty cycle | Continuous |
Coil data -25 and 30Amp,600volt three pole normally open (3.P.N.O)
Steveco Number | Voltage AC | Ress DC OHMS | Current MA | Nominal VA | Max. inrush |
LCK3-160 AMC2-163 | 24 | 9.2 | 187 | 4.5 | 52 |
LCK3-161 AMC2-164 | 120 | 180 | 37 | 4.5 | 52 |
LCK3-162 AMC2-165 | 208/240 | 720 | 19 | 4.5 | 52 |
Contact ratings –25 and 30Amp,600volt three pole normally open (3.P.N.O)
Type | Voltage | 277VAC | 480VAC | 600VAC |
LCK3-160 thru LCK32162 | Full load | 25 A. | 25 A. | 25 A. |
150 A. | 125 A. | 100 A. | ||
40 A. | 40 A. | 40 A. | ||
LCK3-163 thru LCK3-165 | Full load | 30 A. | 30 A. | 30 A. |
180 A. | 150 A. | 120 A. | ||
50 A. | 50 A. | 50 A. |
Coil data -40 Amp ,600 volt three pole normally open (3.P.N.O)
Steveco Number | Coil Voltage AC | Ress DC OHMS | Current MA | Nominal VA | Max. inrush VA |
LCK3-170 | 24 | 7.2 | 187 | 4.5 | 52 |
LCK3-171 | 120 | 180 | 37 | 4.5 | 52 |
LCK3-172 | 208/240 | 720 | 19 | 4.5 | 52 |
Contact ratings -40 Amp ,600 volt three pole normally open (3.P.N.O)
Type | Voltage | 277VAC | 480VAC | 600VAC |
LCK3-170 thru LCK3-172 | Full load | 40 A. | 40 A. | 40 A. |
240 A. | 200 A. | 160 A. | ||
50 A. | 50 A. | 50 A. |
Coil characteristics
Induct FLA | Frequency Hz. | Max. inrush | Sealed (Max.) | ||
VA | Watts | VA | Watts | ||
50 | 50/60 | 240/204 | 100.8/84 | 50.4/36.5 | 10.8/8 |
60 | 50/60 | 240/204 | 100.8/84 | 50.4/36.5 | 10.8/8 |
75 | 50/60 | 300 | 120 | 26 | 8.5 |
92 | 50/60 | 300 | 120 | 26 | 8.5 |
Steveco | Coil volts | Induct FLA | Resistive | Locked Rotor | @Line voltage |
LCK3-459 | 24V | 50 Amp | 65 Amp | 300 Amp | 120V |
LCK3-460 | 120V | 50 Amp | 65 Amp | 300 Amp | 240V |
LCK3-461 | 208/240V | 50 Amp | 65 Amp | 300 Amp | 480V |
200 Amp | 600V |
Steveco | Coil volts | Induct FLA | Resistive | Locked Rotor | @Line voltage |
LCK3-463 | 24V | 60 Amp | 75 Amp | 360 Amp | 120V |
LCK3-464 | 120V | 60 Amp | 75 Amp | 360 Amp | 240V |
LCK3-465 | 208/240V | 60 Amp | 75 Amp | 300 Amp | 480V |
240 Amp | 600V |
Steveco | Coil volts | Induct FLA | Resistive | Locked Rotor | @Line voltage |
LCK3-467 | 24V | 75 Amp | 90 Amp | 450 Amp | 240V |
LCK3-468 | 120V | 75 Amp | 90 Amp | 375 Amp | 480V |
LCK3-469 | 208/240V | 75 Amp | 90 Amp | 300 Amp | 600V |
LCK3-471 | 24V | 90 Amp | 120 Amp | 450 Amp | 240V |
LCK3-472 | 120V | 90 Amp | 120 Amp | 450 Amp | 480V |
LCK3-473 | 208/240V | 90 Amp | 120 Amp | 360 Amp | 600V |