Short Description:
DZ30-32 is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V or below for protecting circuit from overload and short circuit. This product has advantages of high breaking capacity, small volume, width is only 18mm. It conforms with the standards of IEC60898.
1.Application
DZ30-32 is used in the single phase circuit of AC 50Hz/60Hz, rated voltage 230V or below for protecting circuit from overload and short circuit. This product has advantages of high breaking capacity, small volume, width is only 18mm. It conforms with the standards of IEC60898.
2. Main Technical
Parameter
Type | DZ30-32 |
Pole | 1P+N |
Rated current (A) | 6,10,16,20,25,32 |
Rated voltage(V) | 230 |
Type of instantaneous release | C |
Rated making/breaking capacity Im(A) | 4500 |
3. Applicable
conducting wire:
Rated current(A) | Norminal cross section of wire mm2 |
In ≤ 6 | 1 |
6 < In ≤ 13 | 1.5 |
13 < In ≤ 20 | 2.5 |
20 < In ≤ 25 | 4 |
25 < In ≤ 32 | 6 |
4. The over-current
protection property
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | Note |
Cold position | 1.13In | t ≥ 1h | Non-release | - | |
30 ± 2oC | Carried out immediately after previous test | 1.45In | t<1h | Release | - |
Cold position | 2.55In | 1s < t < 60s | Release | Current smoothly rises to specified value within 5s | |
-5~+40oC | Cold position | 5In | t ≥ 0.1s | Non-release | Type C |
Cold position | 10In | t < 0.1s | Release | Type C |