Short Description: 
Application Double insulation,electron-beam cross linked cables for photovoltaic power stationConstruction Conductor:Tinned copper,according to the VDE 0295IEC 60228,Class5Insulation:Polyolefin copolymer electron-beam cross-linked Outer sheath:Poly
Application
Double insulation, electron-beam cross linked cable for photovoltaic power station
Construction
Conductor: Tinned copper,according to the VDE 0295/IEC 60228, Class5
Insulation: Polyolefin copolymer electron-beam cross-linked
Outer sheath: Polyefin copolymer electron-beam cross-linked
Sheath color: Black/Red/Blue or as per customer’s requite.
Technical Specification
Nominal Voltage: Uo/U=600/1000VAC, 1000V/1800VDC
Test Voltage: 6500V , 50Hz, 5Min.
Temperature Rating: 45℃upto+125℃; -40℉upto+257℉
Ambient temperature: 25 year(TUV); -40℃upto+90℃
-40℉upto+194℉
Max.Short circuit temperature: 28℃, +536℉
Bending Radius: Fixed installation > 4X; Occasionally moved > 5X
Dimensions Parameter
Construction  | Conductor Construction  | Conductor∅  | Outer∅  | Resistance Max  | Current Carring Capacity  | 
N*mm²  | n/m  | mm  | mm  | Ω/Km  | A  | 
1*1.5  | 30/0.25  | 1.58  | 4.90  | 13.30  | 30  | 
1*2.5  | 50/0.25  | 2.02  | 5.45  | 7.98  | 41  | 
1*4.0  | 56/0.30  | 2.30  | 6.10  | 4.75  | 55  | 
1*6.0  | 84/0.30  | 3.42  | 7.20  | 3.39  | 70  | 
1*10.0  | 142/0.30  | 4.56  | 9.00  | 1.95  | 98  | 
1*16.0  | 228/0.30  | 5.60  | 10.20  | 1.24  | 132  | 
1*25.0  | 361/0.30  | 6.95  | 12.00  | 0.795  | 176  | 
1*35.0  | 525/0.30  | 8.74  | 13.80  | 0.565  | 218  | 
1*50.0  | 720/0.30  | 9.20  | 14.80  | 0.393  | 280  | 
1*70.0  | 988/0.30  | 11.00  | 16.90  | 0.277  | 350  | 
1*95.0  | 1349/0.30  | 12.50  | 18.70  | 0.21  | 410  | 
1*120.0  | 1691/0.30  | 14.20  | 20.70  | 0.164  | 480  | 
The current-carring capacity is under the situation of laying the single cable in air.
The product’s detailed description please refer to the specification for approval
Advantages
Electron-beam cross-linked compounds
UV, ozone and hydrolysis resistant
High temperature resistant, the materials do not melt or flow
Good cold flexibility
Very long service life > 25 years at 90℃
Compatible to all popular connectors